Liberator extracts smoke and hot gases in the event of a fire. It is suited to most industrial and commercial buildings and can provide both day to day and smoke ventilation. It fulfills the time/temperature requirements of EN 12101-3, achieving F200 (200°C/120 min), F300 (300°C/60 min) and F400 (400°C/ 120 min) in accordance with EN 12101-3.
The Liberator smoke extraction fan is available in roof or wall-mounted versions:
The shutter version with a flap as termination (WL / FLAP) is opened by a gas spring and is pulled closed by a cable that is operated by a rotary electric motor. In the event of fire, this flap is locked in the open position.
The shutter version with a louvred ventilator as termination (WL / FCO) is closed and held closed by a rotary electric motor. In the event of fire, the louvres open under force of the spring, and are held open. This version is suitable only for installation into the wall.
Both shutter versions have fusible links to open the shutter at a pre-defined temperature.
Finishes
All steel components are polyester powder coated to RAL 7032.
Bases and installation
WL / FLAP can be orientated at any angle from the horizontal to the vertical. For all Liberators, their wide range of base types and the fact that they are lightweight means that they can be installed into nearly any type of roof or wall structure.
Certification
Liberator has been successfully tested in accordance with EN 12101-3: 2002, Smoke and Heat Control Systems - Specification for powered smoke and heat exhaust ventilators. Complete CE Certificates of Conformity are available.
Liberator meets the following time/ temperature classifications of EN 12101-3: F200 (200°C for 120 minutes), F300 (300°C for 60 minutes) and F400 (400°C for 120 minutes).
Performance
Liberator produces airflows of between 3.6 m³/s (12,900 m³/h) and 8.9 m³/s (32,050 m³/h). Its noise output ranges from 58 to 87 dB(A) at 3m (sound pressure level). It is available either as single or two speed.
However many projects require extract systems that are outside of the standard Liberator range, either in terms of the extract rate required, or the pressure drop of the system through which the fan is extracting. Please contact Colt.
We provide a pre-order design service. We also offer complete project management, installation, wiring and commissioning, which means that we take complete responsibility to ensure that the product is in full working order within one package of works.
Please contact us for more information relating to the application, specification, installation or servicing of this product.
Liberator powered ventilator - for extraction of smoke and hot gases in the event of a fire as well as day to day ventilation.
Installation options
Shutter version with a flap as termination: opened by a gas spring and closed with a cable operated by a rotary electric motor. In the event of a fire, this flap is locked in the open position. Fusible links to open the shutter at a pre-defined temperature.
Shutter version with a louvred ventilator as termination: opened by a spring mechanism and closed by a rotary electric motor. Fusible links as additional safeguard to open the shutter at a pre-defined temperature.
Maximum 87 dB(A) at 3m
Tested in accordance with EN 12101-3: 2002 and fully CE marked.
Temperature and time classification to BS EN 12101-3